Siemens S7-1200 Ethernet
Supported Series: Siemens S7-1200
HMI Setting
Items
Settings
Note
Protocol
Siemens S7-1200
Connection
Ethernet
Port No.
102
PLC station No.
2
Address list
Type
Device register
HMI register
Format
Range
Note
Bit
I
I
M d.o
d:0--9999
o:0-7
Q
Q
Q d.o
d:0--9999
o:0-7
M
M
M d.o
d:0--9999
o:0-7
DB0.DB-DB99.DB
DBxDB
DBxDB nndddd.o
nn:0-9999,
dddd:0-9999,
o:0-7
nn: DB No.
dddd: address value
o: digit address
Word
M
MB
MB d
d:0-99999
M
MW
MW d
d:0-99999
MW0=MB(0~1)
MW2=MB(2~3)
Address value is a multiple of 2
M
MD
MD d
d:0-99999
MD0=MB(0~3)
MD4=MB(4~7)
Address value is a multiple of 4
I
IW
IW d
d:0-99999
Q
QW
QW d
d:0-99999
DB0.DB-DB99.DB
DBxDBB
DBxDBB nndddd
nn: 0-9999
dddd:0-9999
nn: DB No.
dddd: address value
DB0.DB-DB99.DB
DBxDBW
DBxDBW nndddd
nn:0-9999
dddd:0-9999
nn: DB No.
dddd: address value
Address value is a multiple of 2
DB0.DB-DB99.DB
DBxDBD
DBxDBD nndddd
nn:0-9999
dddd:0-9999
nn: DB No.
dddd: address value
Address value is a multiple of 4
Communication settings
1) Enable HMI Ethernet in [Project Settings];
2) Set PLC IP in [Device IP] settings;
✎Note:
The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
PLC settings
1) Add BD
Please uncheck [Symbolic access only] option;
2) Address settings, using BD2 as example.
DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
2 represent DB block number
xxxx represent address
Such as:
DBxDBB20000 = DB2.DBB0
DBxDBW20004 = DB2.DBW4
How to connect with S7-1200 Firmware V4.0
1) PLC configuration
2) Double click [device configuration] in Siemens via software
3) Double click [protection] to enter protection configuration screen
4) Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
5) DB settings
Right click [DB], select [properties]
Uncheck [optimized block access]
Communication cable